Electronics Agents

Share us

Power Castle Series Online HF UPS 5-6KVA 120VDC

PC05L,PC05S ,PC06L, PC06L

Description

POWER Castle Series Online? HF UPS 5-6 Kva-120Vdc

1.DSP control ,with excellent performance and comprehensive protections for load and UPS ;???????????????????????????

2. Output power factor 0.8,offering more stronger load capability;

3.Intelligent fan speed control ,with 4 levels varying according to load and temperature;

4.Wide input range ,support kinds of generator;

5.Compact size and 120Vdc. Less batteries quantity, more economy, safety and easy use;

6. EPO(emergency power off);?????????????????

7.Event log up to 100 events, recording UPS running time and critical memories ;

8.Intelligent N+X parallel redundancy, up to 6units;

9.AC and cold start function;

10. Human friendly large LCD, with plenty operation information;

11. Frequency convertor mode(input/output 50/60Hz or 60/50Hz);

12. Multiple communication ports ?SNMP/AS400(optional);????

13. Intelligent DSP charger 20A, battery? inverse proection, 3 stages charging process;



Technical Specification

?

- - - -
Model | PCN05S | PCN05L | PCN06S | PCN06L |
Capacity(Kva/kW) | 5KVA/4.0kW | 5KVA/4.0kW | 6KVA/4.8kW | 6KVA/4.8kW |
Phase | 1/1PHASE, 1wire+N+G |
Input ?PF | ≥0.99 |
Input voltage | Low transfer | L-N:176 VAC ± 3% @ 100% load;130 VAC ± 3% @ 50% load |
Low back | L-N:188 VAC ± 3% @ 100% load,142 VAC ± 3% @ 50% load |
High transfer | L-N:286 VAC ± 3% |
High back | L-N:270 VAC ± 3% |
Input frequency range | 40-70hz |
Battery |
Rating/type | 12V/9Ah | depend on external battery | 12V/9Ah | depend on external Battery |
quantity | 10 | depend on external battery? | 10 | depend on external Battery |
Back up time | 4-10mins (depends on load) | 3-8mins (depends on load) |
DC voltage | 120Vdc |
Charge voltage | 137Vdc |
Recharging current | 1A | 5/10A | 1A | 5/10A |
Output |
Output ?P.F | 0.8 |
Output voltage | 220/230/240Vac +/-1%(static) |
Frequency | 46~54Hz or 56~64Hz (Line mode)
50/60Hz ± 0.1Hz ( Battery mode) |
Crest factor | 3:1(max) |
Wave distortion | Less than 2%(linear load), Less than 4% Non-linear load |
Over load | 105% Efficiency | 90%(full load) |
Transfer time | 0ms (AC-Battery); |
0 ms(bypass-inverter) |
Indicator |
LCD Panel | UPS status, Load level, Load watt,Load VA,Battery level, Input/Output voltage, output current,Bus voltage, Temp, and warning and fault code and events |
Alarm |
Battery Mode | Sounding every 4 seconds( can mute) |
Low Battery | Sounding every second |
Overload | Sounding every second |
Fault | Continuously sounding |
Management |
Smart RS-232/USB | Supports Windows? 2000/2003/XP/Vista/2008, Windows? 7, Linux, Unix, and MAC |
Optional | SNMP/AS400/USB |
Environment |
Operation Humidity | 0-90 % RH (non-condensing) @ 0- 40°C |
Noise Level | Less than 55dBA @ 1 Meter | Less than 58dBA @ 1 Meter |
Physical |
Net Weight (KG) | 45 | 18 | 45 | 18 |
Gross Weight(KG) | 52 | 20 | 52 | 20 |
Unit Dimension (D*W*H)mm | 510*250*465 | 507*230*385 | 510*250*465 | 507*230*385 |
Packing (D*W*H)mm | 650×363×565 | 605*330*477 | 650×363×565 | 605*330*477 |
? | ? | ? | ? | ? | ? | ? | ? | ? | ? |
- - - -

Note:All specifications subject to change without further notice; customized specifications are acceptable

cheap prodocuts, china suppliers,

Read More

Previous

PM RS232 Online High Frequency UPS 5kva Double Conversion Cold Start...

Previous

Power Safe Series DSP Online LF UPS 4-40KVA...

Shenzhen HuaRuiDi Science & Technology Co., Ltd.

Online High Frequency UPS,Online Low Frequency UPS ,Line Interactive UPS

Address: 4th floor No.7 buliding,Changxing High-Tech Industrial Park,
shenzhen, guangdong
China, 518000

Tel: 86-755-81737467
Fax: 86-755-81737252

H5响应式定制设计
26种语言,SEO营销型网站


H5/响应式/营销型企业网站; 26种语言扩展;
覆盖: 英文、法语、德语、西班牙语、葡萄牙语、俄语、阿拉伯语、波斯语、日语、韩语
了解更多